The free EuroSoft® connect App allows to transmit measured values to iOS and Android smartphones or tablets via QR code or Bluetooth®.
The BLUELYZER® C1 is built for professionals who value accuracy, simplicity, and reliability. It delivers precise measurement and analysis for the adjustment, maintenance, and inspection of small to medium-sized heating systems.
Beyond flue gas analysis, the BLUELYZER® C1 also measures differential pressures and temperatures, enabling quick determination of flow and return values. Integrated CO ambient monitoring adds an extra layer of safety with two freely adjustable alarm thresholds.
Seamless data transfer to the EuroSoft® connect app enables efficient, professional documentation. Customizable measurement programs and parameters provide maximum flexibility in everyday workflows, making the instrument adaptable to each user’s needs.

| General data |
|
| Dimensions H x W x D |
178 x 78 x 45 mm |
| Weight |
approx. 370 g |
| Material housing |
2K ABS + PC / TPE |
| Display type |
3.5" color TFT |
| Air pressure range |
750 to 1,100 hPa |
| Humidity range |
20 to 80 % rh |
| Operating temperature |
0 to 40 °C |
| Storage temperature |
-20 to 50 °C |
| Data interface |
Bluetooth® USB-C QR code generator IR / Bluetooth® with optional EUROprinter |
| Connection |
Gas: 1x Ø 8 mm |
| Draft: 1x Ø 7 mm | |
| Pressure: 1x Ø 8 mm (option) | |
| Temperature: 2x thermocouple socket | |
| Power supply |
via USB-C socket and (fast charge) adapter |
| Battery type | rechargeable lithium-ion battery 3.6 V / 4,800 mAh |
| Operating time | approx. 20 hours |
| Memory type | Memory type internal memory (up to 100 measurement reports) |
| Ingress protection rating | IP40 (EN 60529) |
| O2 (oxygen) |
|
| Measuring range |
0 to 21.0 vol.-% |
| Accuracy |
±0.2 vol.-% RDG |
| Resolution |
0.1 vol.-% |
| Response delay (t90) |
< 30 seconds |
| CO (carbon monoxide) |
|
| Measuring range | 0 to 2,000 ppm (max. 6,000) |
| Accuracy |
±5 ppm (< 50 ppm) |
| ±5% RDG (> 50 ppm) |
|
| Resolution |
1 ppm |
| Response delay (t90) |
< 60 seconds |
| Flue gas temperature |
|
| Measuring range |
0 to 1,150 °C |
| Accuracy |
±1 °C + 1 digit (< 300 °C) |
| ±1 % RDG (> 300 °C) | |
| Resolution |
0.1 °C |
| Response delay (t90) |
< 30 seconds |
| Combustion air temperature |
|
| Measuring range |
-20 to 200 °C |
| Accuracy |
±3 °C + 1 digit (-20 < 0 °C) |
| ±1 °C + 1 digit (0 < 200 °C) | |
| Resolution |
0.1 °C |
| Response delay (t90) |
< 30 seconds |
| Draft/pressure |
|
| Measuring range |
±70 hPa (draft) |
| ±150 hPa (pressure) | |
| Accuracy | ±0.02 hPa (< 2.00 hPa) |
| ±1 % RDG (> 2.00 hPa) |
|
| Resolution |
0.01 hPa (< 20 hPa) |
| 0.1 hPa (> 20 hPa) |
|
| Max. overload | 1,350 hPa |
| Response delay (t90) | < 10 seconds |
| Option: COhigh (carbon monoxide) | |
| Measuring range | 0 to 2.0 vol.-% |
| Accuracy | ±10 ppm (< 200 ppm) |
| ±5 % RDG (> 200 ppm) | |
| Resolution | 1 ppm |
| Response delay (t90) | < 60 seconds |
| Option: NO (nitrogen oxide) | |
| Measuring range | 0 to 5,000 ppm |
| Accuracy | ±5 ppm (< 50 ppm) |
| ±5 % RDG (> 50 ppm) | |
| Resolution | 1 ppm |
| Response delay (t90) | < 60 seconds |
| Option: NOlow (nitrogen oxide low)) | |
| Measuring range | 0 to 300 ppm |
| Accuracy | ±2 ppm (< 40 ppm) |
| ±10 % RDG (> 40 ppm) | |
| Resolution | 0.1 ppm |
| Response delay (t90) | < 60 seconds |
The free EuroSoft® connect App allows to transmit measured values to iOS and Android smartphones or tablets via QR code or Bluetooth®.
The EuroSoft® connect software allows you to transmit measured values to the PC via microSD card and control the instrument remote via Bluetooth®.
Compact infrared high speed thermal printer with magnets on the rear side
For measuring flow velocities, e.g. in ventilation ducts or process air
Flue gas analyzer kit for all fuels to set up heating systems as well for NOx measurements (e.g. for CHPs).
Optimal for HVAC professionals for accurate adjustments or inspections of oil, gas and solid fuel heating systems.